<v Spyder>You're listening to the Pool Envy podcast. Code, compliance, craftsmanship, hosted by Jason Davies. Let's dive in.

00:00:11.440 --> 00:00:21.535
<v Jason>The message shows up every fall. New heater keeps tripping? Must be a bad board. Nope. Nine times out of 10, it isn't the box, it's the supply.

00:00:21.535 --> 00:00:53.595
Today, we're going to keep your heater out of the drama and your name off Facebook by sizing gas piping, meter, and regulators the right way. In a few minutes, you'll know how to count BTUs, pick a sizing table, talk to the utility like a professional, and document the installation so nobody plays the blame game. Heaters don't run on vibes. They run on pressure and volume. If the meter, regulators, or piping can't deliver, the heater locks out and gets blamed for being defective.

00:00:54.720 --> 00:01:40.275
We keep projects calm by aligning scope to code and by checking a few outcomes, not DIY ing the gas work. This episode explains what good looks like under IFGC four zero two, NFPA 54, so owners and builders can communicate clearly. Sizing and adjustments belong to licensed pros and your authority having jurisdiction. Two books run the show, IFGC, International Fuel Gas Code, C section four zero two, gas piping sizing. It tells you to size your total connected load, length, specific gravity, pressure, and an allowable pressure drop using tables or equations.

00:01:40.435 --> 00:02:24.100
NFPA 54, ANSI z two two three dot one, national fuel gas code. Same principles, jurisdictions adopt IFGC, NFPA 54, or both. Your authority having jurisdiction will tell you which they enforce. We size by BTUs per hour, the equivalent length, and choose a method table the authority having jurisdiction recognizes and confirm the meter regulators can deliver the load at pressure. And for those of you looking for very specific details, a BTU per hour is about 251.9958 calories.

00:02:24.660 --> 00:02:28.740
We're basing that on 4.186 joules equaling one calorie.

00:02:29.125 --> 00:02:30.645
<v Spyder>Let's dive in.

00:02:30.645 --> 00:03:04.945
<v Jason>Instead of how to, here are five outcomes your licensed contractor should be able to show you in writing with the code table they used. Total connected load documented. A one page list of every gas appliance, current appliances plus future in the near with BTU per hour nameplates added up. The outcome of this is the total load matches the basis used in the table sizing guide of IFGC four zero two NFPA 54. Pretty simple.

00:03:04.945 --> 00:03:26.730
Walk around the house, add up everything that has gas going into it, come up with a number, compare it. Checkpoint number two, equivalent length identified. A simple sketch with the longest run and fitting count called out. The outcome you want here, the table selection and segment sizes reflect the equivalent length. IFGC four zero two again.

00:03:27.825 --> 00:03:57.565
Checkpoint number three, table and pressure stated. The plan names, the code edition, table, delivery pressure, for example, seven to 14 inches of water column or two psi with downstream regulators and allowable pressure drop. This way, everybody is reading the same table that the authority having jurisdiction enforces. IFGC four zero two NFPA 54. Checkpoint four, meter and regulator capacity confirmed.

00:03:58.445 --> 00:04:15.370
This is a hard one. You're gonna have to look at the meter. But the utility meter rating is usually in cubic feet per hour, and regulator model outlet pressure are listed and adequate for the total load. The supply capacity is proven before scheduling. Checkpoint five, startup pressure is recorded.

00:04:16.090 --> 00:04:36.810
It's time for that Muppet song about the manometer. Manometer readings for static and at fire pressure at the heater are logged with photos. Take a picture of what's on the screen. What should happen there is the pressure stays within the heater spec at load. If not, upstream corrections need to be made.

00:04:36.810 --> 00:05:03.235
Follow those manufacturer specifications plus IFGC and FPA 54 intent. If your method is guess, replace, repeat, you're running a casino, not a project. Paper beats opinions. So here's what you should include. A one page gas schedule, total BTU load, delivery pressure, table used, IFGC NFPA 54, allowable pressure drop, equivalent length, and selected pipe sizes by segment.

00:05:04.540 --> 00:05:31.210
On the utility side, the meter size requested is confirmed. Regulator, model, and outlet pressure. For your startup log, date, ambient temperature, static firing pressures at the appliance, and any error codes if you made them or created them, and a photo of the manometer settings. Basically, it's on paper, it's not gonna be a fight down the road. Undersized meters.

00:05:31.530 --> 00:05:52.865
For example, after adding a 400,000 BTU heater, the meter never knew. Two PSI gas system with downstream line regulators at branches. A plant sees the wrong pressure. Very skinny run to the pad table says increase the pipe size and nobody did. The regulator stack is wrong.

00:05:52.865 --> 00:06:06.350
Venting orientation or the outlet set point mismatch to heater spec. Branch loads miscounted. Future grill, fire feature ignored. And no field verification. If you don't have a manometer, you're guessing.

00:06:07.150 --> 00:06:29.990
Basically, if the heater trips every night at 9PM, it must be haunted, right? So that time of year. Or maybe the heater flips off when the range furnace and spa all fire at the same time because, you know, math. I remember one incident where we had a pool heater being repiped and the gas valve was a little sluggish. And that's because the upstream pressure was somewhere around 27 inches of water column.

00:06:29.990 --> 00:06:50.445
That's where the gas pros had to go adjust the meter down and all was well. It definitely answered the question of why things weren't working right. A few notes here too on the authorities having jurisdiction. Additions vary by state and city. In plain English, ask your inspector which code set and tables they use today, and then put that on your plan.

00:06:50.780 --> 00:06:57.100
The principles don't change, load, length, pressure drop, but the table choice must match your jurisdiction.

00:06:57.180 --> 00:06:58.540
<v Spyder>Let's dive in.

00:06:58.620 --> 00:07:19.155
<v Jason>To my homeowner friends, here are six questions before you install a heater. What's my total BTU load including future grill fire generator? What code table are you using? IFGC, NFPA 54, and what pressure does it assume? Number three, will my meter regulators be upgraded if the load requires it?

00:07:19.520 --> 00:07:41.805
Four, show me the pipe sizes by segment on a sketch. Number five, on startup, will you record static and firing manometer settings? And number six, what do I do if there's a lockout? Who do I call, you or the manufacturer? On the builder side, inventory all the BTUs for all appliances, including near future ads.

00:07:42.765 --> 00:07:58.980
Number two, measure the equivalent length and pick the correct table. State which one. Number three, right size piping by segment. Verify meter capacity and regulator set points before scheduling. Coordinate the utility.

00:07:59.140 --> 00:08:19.045
That's number four. In writing when the meter upgrade is needed. So for example, small regulator manometer on startup. Keep the log with photos and save it. Label the plan with code addition, table, pressure, and allowable drop.

00:08:20.520 --> 00:08:31.480
And lastly, no blame ping pong. Bring the paper to the conversation. What's in writing doesn't need to have a discussion. Heaters don't fail inspections. Plans do.

00:08:31.720 --> 00:08:51.990
Count the BTUs, pick the table, coordinate the meter and regulators, and prove it with a manometer. That's how we do it every time. Just copy us. Quiet, precision, licensed, code compliant, no drama. Licenses, Florida, CPC 1460695.

00:08:52.470 --> 00:09:21.860
Wisconsin, electrical and HVAC, 1543940. Texas, TICL 135O, and Rail 635643. This episode is for education and coordination. All gas work must be performed by licensed professionals under the authority having jurisdiction and per applicable codes and manufacturer instructions. In Wisconsin, services are performed and provided under the appropriate license in the state of service.

00:09:21.860 --> 00:09:29.305
Always remember to confirm your local adoption additions with your authority having jurisdiction. Have a great week, everybody, and we'll see you next time.

00:09:29.305 --> 00:09:43.305
<v Spyder>Thanks for listening to the Pool Envy podcast, where licensed pool professionals speak up. Hosted by Jason Davies, licensed across Wisconsin, Florida, and Texas. For more insights, subscribe and join us next time.